Sabtu, 27 Agustus 2011

CONTOH HASIL INFRAREED


HERMOGRAPHIC REPORT
Company
GRAHA KENCANA                              13
Problem #
HOT POINT
IDENTIFICATION
Location Name
Equipment
AREA ROOF RUANG LIFT
PANEL CT/POMPA                          380 V
PROBLEM DESCRIPTION
THERMOGRAM
TEMPERATURE MEASUREMENTS
Image Date
Target Temperature
Emissivity
Reflected Temp
6/5/2009 1:33:11 SORE
65.0 °C
0.90
OFF
WEATHER
Air Temp
Sky
Wind Speed
From
50°C
CERAH
0 m/s
Distance

Rated Load
Meas. Load
% Load
TERMINASI CONTACTOR NO.5 DAN JOINT PADA THERMIS OVERLOAD HOT POINT,TEMP. 89.0 C ,TEMP NORMAL LAINNYA 60.8 C ,INDIKASI TERMINASI CONTACTOR/THERMIS LOOSE CONNECTION, RESIKO  CONTACTOR TRIP ,BURN.FIRE ..

0.5 - 3 M
HIGH
100
Comments
MAINTENANCE ACTION
Repaired by
Description
REPAIR PRIORITY
Subj. Rating
Temp. Rating
REINSPECTION
Reinspected by
Date
CLEANER DAN KENCANGKAN TERMINASI KABEL IN/OUT DAN JOINT TSB SEGERA/URGENT ACTION
           D
         28.2°C


1



Tidak ada komentar:

Posting Komentar