HERMOGRAPHIC REPORT
|
Company
|
GRAHA KENCANA 13
|
Problem #
|
HOT POINT
|
IDENTIFICATION
|
Location Name
|
Equipment
|
AREA ROOF RUANG LIFT
|
PANEL CT/POMPA 380 V
|
THERMOGRAM
|
TEMPERATURE MEASUREMENTS
|
Image Date
|
Target Temperature
|
Emissivity
|
Reflected Temp
|
6/5/2009 1:33:11 SORE
|
65.0 °C
|
0.90
|
OFF
|
WEATHER
|
Air Temp
|
Sky
|
Wind Speed
|
From
|
50°C
|
CERAH
|
0 m/s
|
Distance
|
Rated Load
|
Meas. Load
|
% Load
|
TERMINASI CONTACTOR NO.5 DAN JOINT PADA THERMIS OVERLOAD HOT POINT,TEMP. 89.0 C ,TEMP NORMAL LAINNYA 60.8 C ,INDIKASI TERMINASI CONTACTOR/THERMIS LOOSE CONNECTION, RESIKO CONTACTOR TRIP ,BURN.FIRE ..
|
HIGH
|
100
|
Comments
|
MAINTENANCE ACTION
|
Repaired by
|
Description
|
REPAIR PRIORITY
|
Subj. Rating
|
Temp. Rating
|
REINSPECTION
|
Reinspected by
|
Date
|
CLEANER DAN KENCANGKAN TERMINASI KABEL IN/OUT DAN JOINT TSB SEGERA/URGENT ACTION
|